You are currently viewing Explosive Demolition of Earthquake-Damaged Buildings in Hassa: What Did Vibration Monitoring Show?

Explosive Demolition of Earthquake-Damaged Buildings in Hassa: What Did Vibration Monitoring Show?

📁 Case Study

After the Kahramanmaraş earthquakes, damaged buildings in the town centre of Hassa, Hatay, had to be removed. The DTEX founding team provided blasting engineering, supervision and consultancy for the explosive demolition of these buildings. This article looks at the ground vibration recorded during the blast of 15 September 2023 and what the measurement tells us.

💡 In short

The highest vibration recorded (peak vector sum) was 1.646 mm/s. The governing component was the vertical one. At its own frequency, it reached 31.9% of the DIN 4150-3 limit for structures most sensitive to vibration.

Site and constraints

  • Location: Town centre of Hassa, Hatay, Türkiye.
  • Buildings: Earthquake-damaged reinforced concrete buildings, both low-rise and multi-storey. Concrete class C30.
  • Layout: Attached buildings sharing common walls with their neighbours.

When buildings are attached, the one being demolished cannot be treated in isolation; the neighbours are part of the interaction. A structural system already weakened by an earthquake also behaves less predictably during demolition than an intact one.

Approach

The method was explosive demolition. DTEX assessment: For a damaged, attached building, explosive demolition does two things. It shortens the time people and machines must work next to the structure, and it ties the collapse to a sequence designed in advance.

The blast was recorded as a full waveform by a calibrated vibration monitor:

  • Instrument: Instantel Micromate, ISEE 10.90FB, serial UM12584
  • Calibration: 28/09/2022
  • Sample rate: 2,048 samples per second
  • Instrument self-test: Passed

Details of the blast design (holes, charges and delay pattern) are outside the scope of this article.

Result: Measured vibration

ComponentPeak particle velocity (mm/s)Dominant frequency (Hz)
Vertical1.62423.8
Longitudinal1.08068.3
Transverse0.725>100
Peak vector sum1.646—

The values were not taken from the instrument’s summary screen. They were recalculated from the 14,567 samples of the raw waveform, and matched the instrument’s own values with a difference of 0.000 mm/s.

Each measured component was compared with the limit at its own dominant frequency:

  • DIN 4150-3, Table 1, Line 3 (structures particularly sensitive to vibration, listed buildings): governing ratio 31.9% (vertical component)
  • DIN 4150-3, Table 1, Line 2 (residential buildings): 18.0%
  • US OSM alternative blasting level criteria (30 CFR 817.67(d)(4), Figure 1): 4.3%

The transverse component lies above 100 Hz, outside the range over which the curves are defined. It was therefore assessed against the 100 Hz limit, the most conservative option.

📜 Regulatory reference

In Türkiye, limit values for blast-induced ground vibration are set in Annex 2 of the Environmental Noise Control Regulation (Çevresel Gürültü Kontrol Yönetmeliği, Official Gazette 30/11/2022, No. 32029). For how we deliver this service, see vibration monitoring and PPV measurement. More completed work is listed among our reference projects.

Values we do not report, and a lesson for 2027

Air overpressure was recorded in the same event. However, the microphone signal saturated at the ceiling of the instrument’s measuring range; in other words, it was clipped. The peak value in the record is therefore not a valid measurement, and we do not present it as a result. The two fields in the record that give the distance to the measuring point also contradict each other, so we do not report distance or scaled distance either.

DTEX assessment: This matters even more from 2027. Paragraph 4 of Article 13/B, added to the Regulation on the Demolition of Buildings (Binaların Yıkılması Hakkında Yönetmelik), requires calibrated vibration and pressure sensors to be used at the moment of blasting. The provision enters into force on 12/08/2027. A calibrated sensor is not enough on its own: the measuring range must also suit the expected level. Otherwise a record is captured but cannot be used.

Video

Two Explosive Demolitions | Hassa, Hatay

⚠️ Disclaimer

This content is for general information and academic/professional discussion only; it does not constitute a design, instruction or procedure for any demolition, blasting or engineering application. Explosives and controlled blasting operations must be carried out by specialists authorised under the relevant legislation, using site-specific calculations and reports. Legislation may change; the current text published in the Official Gazette must be used before any application. DTEX Savunma Madencilik accepts no liability for third-party use of this content.

◆ ◆ ◆

📚 Sources (accessed 2 October 2026)

  1. Instantel Micromate (serial UM12584) event record UM12584_20230915172254, 15/09/2023 — DTEX archive, unpublished measurement record.
  2. DTEX, Blast Vibration Compliance Analysis — Hatay/Hassa 15/09/2023 — internal analysis.
  3. DIN 4150-3, Erschütterungen im Bauwesen – Teil 3: Einwirkungen auf bauliche Anlagen, Table 1.
  4. 30 CFR 817.67, “Use of explosives: Control of adverse effects”, (d)(4) and Figure 1 — law.cornell.edu
  5. Regulation amending the Regulation on the Demolition of Buildings (Binaların Yıkılması Hakkında Yönetmelikte Değişiklik Yapılmasına Dair Yönetmelik) — Official Gazette 12/08/2026, No. 33338. Adds Article 13/B to the main regulation; under Article 14(b) of the amending regulation it enters into force on 12/08/2027. resmigazete.gov.tr
  6. Environmental Noise Control Regulation (Çevresel Gürültü Kontrol Yönetmeliği) — Official Gazette 30/11/2022, No. 32029. resmigazete.gov.tr
  7. DTEX YouTube, “İki Yapının Patlayıcılar ile Kontrollü Yıkımı | Two Explosive Demolitions | Hassa, Hatay”, 15/09/2026 — youtu.be/Ka_mxJEUPtk